- Read this guide entirely before installation.
- This document provides minimum requirements and recommendations for safe and successful installation of SoliTek PV modules and is necessary to retain compliance with IEC 61215, IEC 61730, and UL 61730 standards.
- This guide provides basic information on JSC SoliTek Cells SOLID series photovoltaic modules, including their installation and safe handling.
- All instructions should be read and understood before attempting installation. Contact your dealer or JSC SoliTek Cells for further information if needed.
- This documentation refers to the PV modules themselves and is not a comprehensive installation manual for personnel not specifically trained in PV modules.
- It serves as a general but strictly mandatory reference for the installer. Infringement or inaccurate observance of any clause in this documentation voids the warranty.
- The installer must understand and follow all applicable local, state, and federal regulations and standards for building construction, electrical design, fire, and safety.
- Check with local authorities for permitting requirements before installing or maintaining PV modules, and become familiar with mechanical and electrical requirements for photovoltaic systems.
- Tämän oppaan ohjeiden noudattamatta jättäminen voi vahingoittaa järjestelmän osia, vaarantaa henkilöstön, vahingoittaa omaisuutta tai mitätöidä paneelin takuun.
- Rooftop PV systems should only be installed on dwellings formally analyzed for structural integrity and confirmed to be capable of handling the additional weighted load of PV system components (including PV modules) by a certified building specialist or engineer.
YLEISET VAATIMUKSET
- Lue tämä opas kokonaan ennen asennusta.
- Tämän asiakirjan tarkoituksena on tarjota vähimmäisvaatimukset ja suositukset SoliTek PV -moduulien turvalliselle ja onnistuneelle asennukselle.
- Tämä asiakirja sisältää myös vaatimukset, jotka ovat välttämättömiä, jotta SoliTek PV -moduuli on IEC 61215-, IEC 61730- ja UL 61730 -standardien mukainen.
- Tämä opas sisältää perustiedot JSC “SoliTek Cells” SOLID-sarjan aurinkosähkömoduuleista, niiden asennuksesta ja turvallisesta käsittelystä. Kaikki ohjeet tulee lukea ja ymmärtää ennen asennusta. Jos sinulla on kysyttävää, ota yhteyttä jälleenmyyjään tai JSC "SoliTek Cells" saadaksesi lisätietoja.
- This documentation refers to the PV-modules themselves and is not meant to be a complete installation manual for personnel not specifically trained to PV-modules.
- It serves as a general but strictly mandatory reference for the Installer.
- Tämän dokumentaation minkä tahansa kohdan rikkominen tai epätarkka noudattaminen mitätöi takuun.
- Asentajan on ymmärrettävä ja noudatettava kaikkia soveltuvia paikallisia, osavaltion ja liittovaltion määräyksiä ja standardeja, jotka koskevat rakennusten rakentamista, sähkösuunnittelua, paloa ja turvallisuutta, ja hänen on tarkistettava paikallisilta viranomaisilta sovellettavat lupavaatimukset ennen kuin hän yrittää asentaa tai huoltaa PV-moduuleja. perehtyä aurinkosähköjärjestelmien mekaanisiin ja sähköisiin vaatimuksiin.
- Tämän oppaan ohjeiden noudattamatta jättäminen voi vahingoittaa järjestelmän osia, vaarantaa henkilöstön, vahingoittaa omaisuutta tai mitätöidä paneelin takuun.
- Katolle asennettavat aurinkosähköjärjestelmät tulisi asentaa vain asuntoihin, joiden rakenteellinen eheys on virallisesti analysoitu ja sertifioitu rakennusasiantuntija tai insinööri on vahvistanut, että ne pystyvät käsittelemään aurinkosähköjärjestelmän komponenttien painotetun lisäkuorman, mukaan lukien aurinkosähkömoduulit.
- For your safety, do not attempt to work on a rooftop until safety precautions have been identified and taken, including, without limitation fall protection measures, ladders or stairways, and personal protective equipment (PPE).
- For your safety, do not install or handle PV modules under adverse conditions, including, without limitation strong or gusty winds, and wet or frosted roof surfaces.
- Tasainen PV-moduulirakenne koostuu laminoidusta aurinkokennojen kokoonpanosta, joka on kapseloitu eristysmateriaaliin kahdessa lasilevyssä.
- Säilytä tämä asiakirja turvallisessa paikassa tulevaa tarvetta varten.
- Älä yritä purkaa moduulia, äläkä poista mitään kiinnitettyjä nimikylttejä tai osia! Tämä mitätöi takuun.
Käsittely & Sovellus
KÄSITTELY
- SoliTek PV modules must be transported in the supplied packaging only and kept in the packaging until they are ready to be installed.
- Protect pallets against movement and exposure to damage during transportation. Secure pallets from falling over.
- Älä ylitä pinottavien lavojen enimmäiskorkeutta, joka on ilmoitettu lavapakkauksessa.
- Store pallets in a cool and dry location until the PV modules are ready to be unpackaged.
- SoliTek PV modules are heavy and should be handled with care. Never use the junction box or cables as a grip.
- Do not exert mechanical stress on the cables.
- Never step on PV modules or drop or place heavy objects on them.
- Be careful when placing PV modules on hard surfaces and secure them from falling.
- Broken glass can result in personal injury. PV modules with broken glass cannot be repaired and must not be used.
- Broken or damaged PV modules must be handled carefully and disposed of properly.
SOVELLUS
Rajoitukset
- SoliTek PV modules must be mounted on appropriate mounting structures positioned on suitable buildings, the ground, or other structures suitable for PV modules (e.g. carports, building facades or PV trackers).
- PV modules must not be mounted on moving vehicles of any kind. Modules must not be installed in locations where they could be submerged in water.
- Do not install modules above 2000 m (6561 ft) altitude above sea level
- Keinotekoisesti keskitettyä valoa ei saa suunnata SoliTek PV -moduuleille.
Suositukset
- SoliTek suosittelee, että PV-moduulit asennetaan vähintään 10 asteen kallistuskulmaan, jotta ne puhdistuvat kunnolla sateelta.
- PV-moduulin tai moduulien osittainen tai täydellinen varjostus voi heikentää merkittävästi järjestelmän suorituskykyä.
- SoliTek suosittelee varjostuksen minimoimista ympäri vuoden, jotta aurinkosähkömoduulien tuottaman energian määrä kasvaisi.
- High system voltages could be induced in the event of an indirect lightning strike, which could cause damage to PV system components.
- The open area of wire loops should be minimized in order to reduce the risk of lightning-induced voltage aaltoja.
- Parempi moduuliilmanvaihto ja lyhyemmät liitäntäkaapelit lisäävät sähköenergian tuotantoa.
Bifacial-moduuleille:
- On suositeltavaa nostaa PV-paneelin korkeutta maasta, jotta enemmän valoa pääsee moduulin alle ja sitten heijastumaan
- Bifacial vahvistus kasvaa merkittävästi, jos moduulit asennetaan valkoisten (korkea albedo-arvo) valoa heijastavien pintojen yläpuolelle.
Sähköasennus
TURVALLISUUS
- PV-moduulit voivat tuottaa virtaa ja voltage kun se altistetaan minkä tahansa voimakkaalle valolle. Sähkövirta kasvaa valovoimakkuuden kasvaessa. DC voltage 50 volttia tai enemmän on mahdollisesti tappava. Kosketus valossa toimivan aurinkosähköjärjestelmän jännitteellisiin piireihin voi johtaa tappavaan sähköiskuun.
- Katkaise aurinkosähkömoduulien jännite poistamalla ne kokonaan valosta tai peittämällä niiden etupinta läpinäkymättömällä materiaalilla. Noudata jännitteisten sähkölaitteiden turvallisuusmääräyksiä työskennellessäsi valolle altistuvien moduulien kanssa. Käytä eristettyjä työkaluja äläkä käytä metallikoruja työskennellessäsi aurinkosähkömoduulien kanssa.
- Välttääksesi valokaaren ja sähköiskun, älä irrota sähköliitäntöjä kuormitettuna. Virheelliset liitännät voivat myös aiheuttaa valokaaren ja sähköiskun. Pidä liittimet kuivina ja puhtaina ja varmista, että ne ovat asianmukaisessa toimintakunnossa. Älä koskaan työnnä metalliesineitä liittimiin tai muokkaa niitä millään tavalla sähköliitännän varmistamiseksi.
- Do not touch or handle PV modules with broken glass unless the PV modules are first disconnected, and you are wearing proper PPE. Avoid handling PV modules when they are wet unless cleaning the PV modules as directed in this manual. Never touch electrical and wet connections without protecting yourself with insulated gloves.
- The modules are qualified for Class II protection against electrical shock, in accordance with clause 4 of IEC 61730-1:2016, which can be used in systems operating at > 50 V DC or >240 W, where general contact access is anticipated and modules qualified for safety through UL 61730 within this application class are considered to meet the requirements of Safety Class II.
- Aurinkosähköjärjestelmien asentaminen vaatii erityistaitoja ja -tietoja. Sen saa suorittaa vain pätevä ja erityisesti opastettu henkilökunta. Asentaja ottaa kaikki loukkaantumisriskit, mukaan lukien sähköiskun vaara.
- Käytä vain laitteita, liittimiä, johtoja ja asennuslaitteita, jotka on erityisesti suunniteltu käytettäväksi aurinkosähköjärjestelmässä.
- Before any manipulation at an installed PV plant, switch it off first on the AC-side, and then on the DC side of the inverter or the charge controller.
- Kun irrotat valolle alttiina olevaan aurinkosähkömoduuliin liitetyt johdot, voi syntyä valokaari. Kaaret voivat aiheuttaa palovammoja, sytyttää tulipalon tai muuten aiheuttaa turvallisuusongelmia (jopa tappava sähköisku).
- Tarkista jäljellä oleva tilavuustage before starting and observe the local safety-relevant regulations for such working conditions.
- Normaaleissa olosuhteissa aurinkosähkömoduuli voi tuottaa enemmän virtaa ja/tai tilavuuttatage (tässä: 30 V DC) kuin standarditestiolosuhteissa raportoitu.
- Ota yhteyttä DC voltage 30 V tai enemmän on mahdollisesti vaarallinen. Ole varovainen, kun kytket tai käsittelet moduuleja, jotka ovat alttiina auringonvalolle.
- Kytke sarjaan vain moduuleja, joilla on sama nimellislähtövirta. Jos moduulit on kytketty sarjaan, kokonaistilavuustage on yhtä suuri kuin yksittäisen moduulin summa voltages.
- Liitä vain moduuleja tai moduulien sarjayhdistelmiä, joilla on sama tilavuustage in parallel. If modules are connected in parallel, the total current is equal to the sum of the individual module or series combination currents.
- Käytä aina samantyyppisiä moduuleja tietyssä aurinkosähköjärjestelmässä.
- If the sum of short circuit currents of the parallel-connected modules exceeds the reverse current, string diodes or fuses have to be used in each string of modules connected in parallel. These string diodes or fuses have to be qualified for the maximum expected current and voltage. The fuse rating value is also corresponds to the maximum reverse current that a module can withstand. The reverse current value can be found on the product label, in the product datasheet or in chapter 8 of the installation manual. Observe the instructions and safety precautions for all other components used in the system, including wiring and cables, connectors, DC-breakers, inverters, etc.
- Käytä sähköasennuksiin hyväksyttyjä turvavarusteita (eristettyjä työkaluja, dielektrisiä käsineitä, kenkiä jne.).
ASETUKSET
- Normaaleissa olosuhteissa aurinkosähkömoduuli joutuu todennäköisesti olosuhteisiin, jotka tuottavat enemmän virtaa ja/tai tilavuuttatage than reported at Standard Test Conditions (STC: 1000 W/ m2, AM 1.5, and 250C/770F cell temperature) or Bifacial nominal power index(BNPl front irradiance 1000 W/m2, back irradiance 135 W/m2 AM 1.5, and 25 OC/770F cell temperature). The short-circuit current (ISC) should be multiplied by a factor of 1.25 and the open-circuit voltage (VOC) tulee kertoa kertoimella 1.25 asti perustuen alimpaan ja korkeimpaan ympäristön lämpötilaan, joka on tallennettu asennuspaikalle määritettäessä komponentin tilavuuttatage nimellisarvot, johtimien virran nimellisarvot, sulakkeiden koot ja PV-lähtöön kytkettyjen säätimien koko.
- Voitagne ovat additiivisia, kun PV-moduulit kytketään suoraan sarjaan, ja moduulivirrat ovat additiivisia, kun PV-moduuleja kytketään suoraan rinnan. Sähköisiltä ominaisuuksiltaan erilaisia PV-moduuleja ei saa kytkeä suoraan sarjaan. PV-moduuleihin liitettyjen sopivien kolmannen osapuolen elektronisten laitteiden käyttö voi mahdollistaa erilaisia sähköliitäntöjä, ja ne on asennettava valmistajan ohjeiden mukaisesti.
- Suurin tilavuustage of serial interconnection of the modules must be less than the maximum certified module’s system voltage. Myös suurin tulotilavuustaginvertterin ja muiden järjestelmän sähkölaitteiden e on otettava huomioon. Avoin piiri voltage of the array string needs to be calculated at the lowest expected a mbient temperature forthe location. The maximal system voltage for the module is indicated in the module’s datasheet.
- Accordingly, for BLACKSTAR, SOLID or MAGNUS series modules, the values of ISC and VOC under STC or BNPI marked on this module should be multiplied by a factor of 1,25 when determining component voltage ratings, conductor current ratings, fuse sizes, and size of controls connected to the PV output. In the USA, referto Section 690-8 of the National Electrical Code (N EC) for an additional multiplying factor of 125 percent (80 percent de-rating) which may be applicable.
YLIVIRTASUOJA (OCPD)
- When the potential reverse current of a PV string exceeds the rated SoliTek PV module series fuse rating (values indicated at the module datasheet) an overcurrent protection device (OCPD) must be used.
- An overcurrent protection device is required for each series string if more than two series are connected in parallel.
- In this case, it is needed to use one fuse per string rated at 1.25 x Isc or higher (Isc is the PV module’s short circuit current at STC). A PV fuse on each PV string will protect the PV modules and conductors from overcurrent faults and help minimize any safety hazards.
- The PV fuse will also isolate the faulted PV string so the balance of the PV system can continue to generate electricity.
- Sulake amp luokitus ≥ 1.25 x Isc
- Valitse seuraava korkeampi standardiluokitus saatavilla olevien PV-sulakkeiden luettelosta.
- Isc = Yhden moduulin oikosulkuvirta vakiotestausolosuhteissa (STC).
- SoliTek-moduulien Isc-arvot huomioon ottaen asennuksessa käytettävien PV-sulakkeiden oikea arvo on 30 A. SoliTek suosittelee PV-sulakkeiden käyttöä sekä positiivisissa että negatiivisissa johtimissa.
KAAPELI JA JOHDOTUS
SoliTek PV -moduuleissa on kaksi tavallista, auringonvaloa kestävää lähtökaapelia, jotka on päätetty PV-liittimillä, jotka ovat valmiita useimpia asennuksia varten. Positiivisessa (+) navassa on urosliitin, kun taas negatiivisessa (-) navassa on naarasliitin. Moduulijohdotus on tarkoitettu sarjakytkentöihin (eli uros- (+)-naarasliitännät (-)), mutta sitä voidaan käyttää myös sopivien kolmannen osapuolen sähkölaitteiden kytkemiseen, joilla voi olla vaihtoehtoisia johdotuskokoonpanoja, kunhan valmistajan ohjeita noudatetaan.
Käytä kenttäjohtoja, joiden poikkipinta-ala on sopiva ja jotka on hyväksytty käytettäväksi PV-moduulin suurimmalla oikosulkuvirralla. Kaikkien johtojen tulee olla kaksoiseristettyjä, silloitettuja kaapeleita, joiden jännite on vähintään 1,8 kV (yli 1500 V vol.tage) ja miniminimellislämpötila 90 ˚C (190 °F). Johdon koko vähintään 4 mm² (12 AWG). Eristystyypin tulee olla sopiva käytettävälle asennusmenetelmälle ja sen on täytettävä IEC 61730 ja turvallisuusluokan II vaatimukset.
- Eristystaso: 1,8 kV (johdin-johdin).
- Lämpötila: vähintään -40 °C - +90 °C (-40 °F - 190 °F).
- Johtimen rakenne: tinattu säikeinen kuparilanka, jonka kuparin puhtaus on yli 99,9 %.
- Ensisijainen eristys: silloitettu polyeteeni (XLPE), auringonvaloa ja kosteutta kestävä, paloa hidastava. Soveltuu maan alle asennettuihin putkiin ja juoksuteihin.
- Eristys (vaippa): termoplastinen, auringonvaloa kestävä, palonestoaine, vedenkestävä.
- Pienin kaapelin ulkohalkaisija eristyksellä – 5,2 mm (2,05 tuumaa).
- Pienin johtimen poikkipinta-ala – 4 mm² (12 AWG).
SoliTek suosittelee, että asentajat käyttävät vain auringonvaloa kestäviä kaapeleita, jotka on hyväksytty tasavirtajohdotukseen aurinkosähköjärjestelmissä. Kaapelit tulee kiinnittää asennusrakenteeseen siten, että vältetään kaapelin ja/tai moduulin mekaaniset vauriot. Älä rasita kaapeleita. Käytä kiinnittämiseen sopivia keinoja, kuten auringonvaloa kestäviä nippusiteitä ja/tai johdinpidikkeita. Vaikka kaapelit ovat auringonvalon ja vedenpitäviä, vältä mahdollisuuksien mukaan suoraa auringonvaloa ja kaapelien upottamista veteen.
Jakorasiasta lähtevien kaapelien vakiopituus on 1,2 m (47,24 tuumaa). Järjestelmässä on tarkoitus kytkeä kaksi paneelia toisiinsa.
MAADOITUS
- Module grounding must be done in accordance with the electrical design and construction specifications, procedures, regulations and other special grounding requirements applicable to the installation sites. If grounding is needed, it should be done accordingly:
Framed type modules grounding
Runkoon maadoitusmerkillä merkittyjä reikiä saa käyttää vain maadoitukseen. Älä poraa ylimääräisiä maadoitusreikiä moduulin runkoon.
The grounding conductor or strap may be copper, copper alloy, or any other material acceptable foruse as an electrical conductor in accordance with local electric codes and regulations.
Maadoitusjohdin on sitten liitettävä maahan sopivalla maadoituselektrodilla.
A bolted connection is required; it incorporates:
- Pultin koko M4.
- Pultin kannan alla olevan hammasaluslevyn tai sahalaitaisen pultin on lävistettävä sähköä johtamattomat pinnoitteet, kuten anodisoitu runko.
- M4-pultille sopiva kiinnitysmutteri.
- Kaikkien laitteiden tulee olla värimetallia, 300-sarjan ruostumatonta terästä tai sopivasti korroosiosuojattuja.
- Suositeltu mutterin lukitusmomentti on 2 Nm÷2.2 Nm (1,48÷1,62 ft-lb).
- Maadoituspultin on mentävä kaikkien liitoselementtien läpi.

- PV-moduulien metallirunkojen maadoitusta varten luetellut ja tunnistetut laitteet saavat maadoittaa moduulin paljaat metallikehykset maadoitettuihin asennusrakenteisiin.
- In any case the grounding screws or other parts have to be used separately from the mounting parts of the module.
- Alternate grounding options built through the mounting system are acceptable as long as they have been IEC and UL approved.
- Grounding resistance of the grounding structure shall be reached according to local regulations, Eurocodes, or other legal normative references.
Frameless type modules grounding
- Due to that modules are without frame, grounding is not forseen. Other PV plant equipment should be grounded according to the local and national electrical codes.
LIITTIMET
- Connectors for SoliTek PV panels are Stäubli MC4-Evo 2. Keep connectors dry and clean and ensure that connector caps are hand-tight before connecting the modules.
- Älä yritä tehdä sähköliitäntää märillä, likaisilla tai muuten viallisilla liittimillä.
- Vältä altistumista auringonvalolle ja liittimien upottamista veteen. Vältä maata tai kattoa vasten lepääviä liittimiä.
- Do not disconnect under load. Faulty connections can result in arcs and electrical shock.
- Tarkista, että kaikki sähköliitännät on kiinnitetty kunnolla. Varmista, että kaikki lukitusliittimet ovat kunnolla kiinni ja lukittu.
OHITUSDIODIT
The PV module’s junction box contains 3 bypass diodes (one in each part of split junction box; Schottky type) connected in parallel with the PV cell strings. In the case of partial shading (hot-spot effect), the diodes bypass the current generated by the non-shaded cells, therebylimiting module heating and performance losses.
Ohitusdiodit eivät ole ylivirtasuojalaitteita. Ohitusdiodit ohjaavat virran kennojonoista osittaisen varjostuksen sattuessa. Näiden diodien ominaisuudet:
- Voitage-arvo - 50 V.
- Nykyinen arvo – 25 A.
PALOLUOJA
- SoliTek SOLID Bifacial- ja Blackstar-moduulit ovat läpäisseet IEC-palotestin ja saavuttaneet syttyvyysluokan A. Palotesti suoritettiin 127 mm:n (5 tuuman) kaltevuudella 300 mm:n (11,81 tuuman) matkalla IEC 61730-2 -standardin kohdan A.2.5 mukaisesti.
- SoliTek SOLID Bifacial has fire rating of 28 according to UL1703-2 standard. SoliTek Blackstar has fire rating of 29 according to UL1703-2 standard.
Mekaaninen asennus
- The mechanical loads described in this manual are the test loads.
- For calculating the equivalent maximum design loads, a safety factor of 1.5 (Design load×1.5 safety factor=Mechanical test load) needs to be considered in compliance with the requirements of the local laws and regulations.
YLEISET VAATIMUKSET
- Modules can be mounted in landscape or portrait orientation. For the bifacial modules, in order to get notable bifacial gain, the distance between the bottom of the modules and the roof or ground surface shall be at least 0,8 m (31,50 inch).
- Also, the bifacial gain increases significantly if modules are installed above white, light-reflecting surfaces (under surfaces with high albedo value).
- If the mounting rails are installed across the module, the bifaciality effect will be lower due to back-side cells shading.
- Noudata asennusjärjestelmän mukana toimitettuja turvallisuusmääräyksiä ja asennusohjeita. Tarvittaessa ota yhteyttä suoraan toimittajaan saadaksesi lisätietoja.
- The modules must be safely set onto the mounting rail.
- The whole rail supporting the photovoltaic system must be strong enough to resist potential mechanical pressures caused either by wind or snow, in accordance with local, regional and state safety (and other associated) standards.
- The mounting system shall be tested and inspected by a third-party testing institution with static mechanical analysis capacity in accordance with local national standards or international standards.
- Before installing modules on a roof, ensure that the roof construction is suitable.
- In addition, any roof penetration required to mount the modules must be properly sealed to prevent leaks.
- Varmista, että asennuskisko ei väänny tai vaikuta moduuleihin, kun se laajenee lämpölaajenemisen seurauksena.
- The module can appear thermal expansion and cold contraction; thus, the interval between two adjoining modules shall be no lesser than 10 mm (0,39 inch).
- Älä yritä porata reikiä lasipintaan ja moduulien kehyksiin, sillä tämä mitätöi takuun.
- The mounting method must not result in the direct contact of dissimilar metals with the aluminum frame of the modules that will result in galvanic corrosion.
Kiinnitysosien tulee olla kestäviä, ruostumattomia ja UV-kestäviä materiaaleja (ruostumatonta terästä ja anodisoitua alumiinia suositellaan).
ASENNUS CL:lläAMPS
- Käytä vähintään 4 laminaatticlamps kiinnittää moduulit asennuskiskoihin. Moduulit clamps metalliosat eivät saa joutua kosketuksiin etu- tai takalasin kanssa. Kun valitset tämän tyyppisen clamp-asennustapa, käytä vähintään neljä clamps jokaisessa moduulissa; kaksi clamps tulee kiinnittää jokaiselle pitkälle sivulle. Paikallisista tuuli- ja lumikuormista riippuen lisäclamps voidaan tarvita sen varmistamiseksi, että moduulit kestävät kuorman.
- Clamps kiristysmomentin tulee olla vähintään 15 Nm (11,06 ft-lb), mutta enintään 20 Nm (14,75 ft-lb). Yleensä 15 Nm (11,06 ft-lb) saavutetaan, kun kaksi alumiinia profiles koskettavat toisiaan. Kun moduuli asennetaan pystysuunnassa kaltevalle katolle, jonka kaltevuus on >45°, tarvitaan lisäkoukku moduulin pohjaan.

SOLID Black, Semi-clear, Satin, Agro Frameless
Poikittaisilla kiskoilla


BLACKSTAR, SOLID Black 35(40) mm, SOLID Semi-clear 35(40) mm, SOLID Satin 35(40) mm, SOLID Agro 35(40) mm, Magnus Framed mounting
- Kun valitset tämän tyyppisen clamp-asennustapa, käytä vähintään neljä clamps jokaisessa moduulissa; kaksi clamps tulee kiinnittää moduulin kummallekin puolelle. Moduulit clamps ei saa joutua kosketuksiin etulasin kanssa, eikä se saa vääristää kehystä.
- Vältä moduulin aurinkokennojen varjostusvaikutuksia clamps.
- The module frame is not to be modified under any circumstances. Do not to block the drain hole of the frame.
- Pituus clamp should be at least 30 mm (1,18 inch).
- Clamp on mentävä moduulikehyksen päälle vähintään 5 mm (0,2 tuumaa), mutta enintään 10 mm (0,4 tuumaa).
Poikittaisilla kiskoilla

Ilman poikittaisia kiskoja tai kiskot ovat kohtisuorassa pitkää sivurunkoa vastaan

Kiinnitysjärjestelmällä

Kiinnitys pulteilla
- Moduuli on kiinnitettävä ja tuettava neljällä ruostumattomasta teräksestä valmistetulla M8-pultilla poikittaistankojen merkittyjen kiinnitysreikien läpi. Kiristysmomentti kiinnitysreikiinamp bolt has to be in range of 8÷10 Nm (5,9÷7,38 ft-lb). The transversal bars positioning is shown in Figure 3.
- If additional mounting points are required, depending on the local wind and snow loads, then a mounting solution with clamplaitteisto on valittava.

- Mounting with bolts can be done only through dedicated predrilled holes in the frame.
- Uusien reikien poraus on kiellettyä ja mitätöi takuun.

KYTKENTÄRASIAN SIJAINTI
- Katso alla olevista kuvista liitäntärasian ja moduulin reunan välinen etäisyys tai muut liitäntärasian sijainnin ja alueiden mitat.

HUOLTO
- Moduulin optimaalisen suorituskyvyn varmistamiseksi SoliTek suosittelee seuraavaa:
- Tarvittaessa moduulin lasietuosa voidaan puhdistaa vedellä ja pehmeällä sienellä tai liinalla.
- Mietoa, hankaamatonta pesuainetta voidaan käyttää pinttyneempien tahrojen poistamiseen.
- Tarkista sähkö- ja mekaaniset liitännät säännöllisesti ja varmista, että ne ovat puhtaita, turvallisia, täydellisiä ja varmoja.
- Ongelmatapauksissa ota yhteyttä valtuutettuun/pätevään henkilöön.
TEKNISET TIEDOT
| Parametri \ Malli | BLACKSTAR B.96 | SOLID Black (Semi-Clear) B.96 35(40) mm | BLACKSTAR Satin B.96 | MAGNUS B.108 |
| Testiolosuhteet | STC | STC | STC | STC |
| Nimellisteho | 455 W | 455 W | 445 W | 510 W |
| Sähkötiedot @STC | ||||
| Suurin teho (Pmax), W | 455 | 455 | 445 | 510 |
| Voitage maksimiteholla (Vmpp), V | 29,71 | 29,71 | 29,40 | 33,34 |
| Virta suurimmalla teholla (Impp), A | 15,31 | 15,31 | 15,14 | 15,30 |
| Open Circuit Voltage (Voc), V | 34,82 | 34,82 | 34,40 | 39,06 |
| Oikosulkuvirta (Isc), A | 15,97 | 15,97 | 15,79 | 15,95 |
| Lämpötiedot | ||||
| Käyttölämpötila-alue | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) |
| Lämpötilakerroin Pmax | -0,362 %/°C (°F) | -0,362 %/°C (°F) | -0,362 %/°C (°F) | -0,362 %/°C (°F) |
| Lämpötilakerroin Voc | -0,265 %/°C (°F) | -0,265 %/°C (°F) | -0,265 %/°C (°F) | -0,265 %/°C (°F) |
| Lämpötilakerroin Isc | +0,036 % /° C (°F) | +0,036 % /° C (°F) | +0,036 % /° C (°F) | +0,036 % /° C (°F) |
| Koko- ja painotiedot | ||||
| Pituus | 1762 mm | 1762 mm | 1762 mm | 1961 mm |
| Leveys | 1134 mm | 1134 mm | 1134 mm | 1134 mm |
| Paksuus | 30 mm | 35(40) mm | 30 mm | 30 mm |
| Paino | 25,5 kg | 35 (36) kg | 25,5 kg | 28,5 kg |
| Asennusmenetelmä | ||||
| Reference to the chapter | 3.3 | 3.3 | 3.3 | 3.3 |
| muu | ||||
| Suurin käänteinen virta, A | 30 | |||
| Fire class, IEC 61730/UL 61730 | A/Tyyppi II | |||
| Järjestelmän enimmäistilavuustage, V | 1500 | |||
Table 9. Electrical and mechanical parameters table.
| Parametri \ Malli | KIINTEÄ Semi- clear B.96 | SOLID Black B.96 | KIINTEÄ Satin B.96 | KIINTEÄ Agro B.64 |
| Testiolosuhteet | STC | STC | STC | STC |
| Nimellisteho | 455 W | 455 W | 445 W | 300 W |
| Sähkötiedot @STC | ||||
| Suurin teho (Pmax), W | 455 | 455 | 445 | 300 |
| Voitage maksimiteholla (Vmpp), V | 29,71 | 29,71 | 29,40 | 19,60 |
| Virta suurimmalla teholla (Impp), A | 15,31 | 15,31 | 15,14 | 15,31 |
| Open Circuit Voltage (Voc), V | 34,82 | 34,82 | 34,40 | 22,76 |
| Oikosulkuvirta (Isc), A | 15,97 | 15,97 | 15,79 | 15,97 |
| Lämpötiedot | ||||
| Käyttölämpötila-alue | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) |
| Lämpötilakerroin Pmax | -0,30 %/°C (°F) | -0,30 %/°C (°F) | -0,30 %/°C (°F) | -0,30 %/°C (°F) |
| Lämpötilakerroin Voc | -0,25 %/°C (°F) | -0,25 %/°C (°F) | -0,25 %/°C (°F) | -0,25 %/°C (°F) |
| Lämpötilakerroin Isc | +0,045 % /° C (°F) | +0,045 % /° C (°F) | +0,045 % /° C (°F) | +0,045 % /° C (°F) |
| Koko- ja painotiedot | ||||
| Pituus | 1772 ± 2 mm | 1772 ± 2 mm | 1772 ± 2 mm | 1772 ± 2 mm |
| Leveys | 1144±2 | 1144±2 | 1144 ± 2 mm | 1144 ± 2 mm |
| Paksuus | 7,2 mm | 7,2 mm | 7,2 mm | 7,2 mm |
| Paino | 33 kg | 33 kg | 33 kg | 33 kg |
| Asennusmenetelmä | ||||
| Reference to the chapter | 3.2 | 3.2 | 3.2 | 3.2 |
| muu | ||||
| Suurin käänteinen virta, A | 30 | |||
| Fire class, IEC 61730/UL 61730 | A/Tyyppi II | |||
| Järjestelmän enimmäistilavuustage, V | 1500 | |||
Table 10. Electrical and mechanical parameters table.
| Parametri \ Malli | SOLID Satin B.96 35 mm | SOLID Satin B. 96 40 mm | SOLID AgroB.64 35 mm | SOLID AgroB.64 40 mm |
| Testiolosuhteet | STC | STC | STC | STC |
| Nimellisteho | 445 W | 445 W | 300 W | 300 W |
| Sähkötiedot @STC | ||||
| Suurin teho (Pmax), W | 445 | 445 | 300 | 300 |
| Voitage maksimiteholla (Vmpp), V | 29,40 | 29,40 | 19,60 | 19,60 |
| Virta suurimmalla teholla (Impp), A | 15,14 | 15,14 | 15,31 | 15,31 |
| Open Circuit Voltage (Voc), V | 34,40 | 34,40 | 22,78 | 22,78 |
| Oikosulkuvirta (Isc), A | 15,79 | 15,79 | 15,97 | 15,97 |
| Lämpötiedot | ||||
| Käyttölämpötila-alue | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) | -40oC ÷ 85oC (-40°F ÷ 185°F) |
| Lämpötilakerroin Pmax | -0,362 %/°C (°F) | -0,362 %/°C (°F) | -0,30 %/°C (°F) | -0,30 %/°C (°F) |
| Lämpötilakerroin Voc | -0,265 %/°C (°F) | -0,265 %/°C (°F) | -0,25 %/°C (°F) | -0,25 %/°C (°F) |
| Lämpötilakerroin Isc | +0,036 % /° C (°F) | +0,036 % /° C (°F) | +0,045 % /° C (°F) | +0,045 % /° C (°F) |
| Koko- ja painotiedot | ||||
| Pituus | 1762 mm | 1762 mm | 1762 mm | 1762 mm |
| Leveys | 1134 mm | 1134 mm | 1134 mm | 1134 mm |
| Paksuus | 35 mm | 40 mm | 35 mm | 40 mm |
| Paino | 35 kg | 36 kg | 35 kg | 36 kg |
| Asennusmenetelmä | ||||
| Reference to the chapter | 3.3 | |||
| muu | ||||
| Suurin käänteinen virta, A | 30 | |||
| Fire class, IEC 61730/UL 61730 | A/Tyyppi II | |||
| Järjestelmän enimmäistilavuustage, V | 1500 | |||
Table 11.Electrical and mechanical parameters table.
- The electrical characteristics are within of the indicated values of ISC (φISC) ±3%, VOC (ϕVOC) ±3,5% and PMPP (ϕPmax) ±5%, under Standard Test Conditions (STC) (irradiance of 1000 W/m²,AM 1.5 spectrum, and a cell temperature of 25°C / 77°F)
- Kaikki SoliTek SOLID PV -paneelit vastaavat sähköturvallisuusluokkaa II.
Vastuuvapauslauseke
- Koska SoliTek ei voi ohjata aurinkosähköjärjestelmän asennusta, käyttöä, käyttöä ja huoltoa tämän ohjeen mukaisesti. SoliTek ei ota vastuuta eikä nimenomaisesti ota vastuuta mistään menetyksistä, vahingoista tai kuluista, jotka johtuvat tällaisesta asennuksesta, käytöstä, käytöstä tai huollosta tai liittyvät siihen millään tavalla.
- SoliTek will not take any responsibility for any possible violation of patent rights and third-party rights that are related to the application of the solar energy system. No permission of patents is given through implication.
- The information of this instruction is from the knowledge and experiences of SoliTek. However, the instructions and suggestions of this instruction do not make an external or internal of guarantee. SoliTek reserves the right to revise this instruction, products and all the information about products without prior notification to customers.
FAQ
- Q: What should I do before installing the PV modules?
- A: Read this entire guide, understand all instructions, and ensure compliance with all local, state, and federal regulations. Consult a certified building specialist for the structural integrity of the dwelling.
- Q: Can I install the PV modules myself without professional training?
- A: This documentation is not a complete installation manual for personnel not specifically trained in PV-modules. It serves as a general but strictly mandatory reference for the installer. Professional installation is highly recommended.
- Q: What happens if I don’t follow the instructions in this guide?
- A: Failure to follow instructions may damage system components, endanger personnel, damage property, or invalidate the panel warranty.
- Q: Is it safe to work on a rooftop during installation?
- A: Do not attempt to work on a rooftop until safety precautions have been identified and taken, including fall protection measures, ladders or stairways, and personal protective equipment (PPE). Avoid adverse conditions like strong winds or wet/frosted roofs.
- Q: How should I store the PV modules before installation?
- A: Store pallets in a cool and dry location until the PV modules are ready to be unpackaged. Do not exceed the maximum stacking height indicated on the packaging.