ABB 7524A63G05

ABB:n CLE-tyyppinen virtamuuntaja, malli 7524A63G05, käyttöohje

Asennus-, käyttö- ja huolto-ohjeet

1. Johdanto

This user manual provides essential information for the safe and effective installation, operation, and maintenance of the ABB Type CLE Current Transformer, Model 7524A63G05. This device is designed for accurate current measurement in industrial electrical systems. Please read this manual thoroughly before attempting any procedures to ensure proper handling and to prevent potential hazards.

2. Tuote ohiview

The ABB Type CLE Current Transformer (CT) is a critical component for monitoring and protecting electrical circuits. It safely steps down high primary currents to a measurable level for instruments, meters, and relays. The Model 7524A63G05 features a robust design suitable for demanding industrial environments.

ABB Type CLE Current Transformer, front-side view

Kuva 2.1: Kaiken kaikkiaan view of the ABB Type CLE Current Transformer. This image displays the robust, dark-colored casing and the transparent terminal cover on top, indicating the primary and secondary connections. The toroidal shape allows for easy integration around a primary conductor.

ABB Type CLE Current Transformer, angled view

Kuva 2.2: Toinen kulmikas view of the ABB Type CLE Current Transformer, highlighting its compact design and the mounting points on the base. The nameplate is visible on the side, providing key operational specifications.

Close-up of ABB Type CLE Current Transformer terminal block and nameplate

Kuva 2.3: A detailed close-up of the terminal block and the product nameplate. The transparent cover protects the secondary terminals (X1, X2) and shows the connection points. The nameplate clearly displays the model number, current ratio, and other electrical specifications.

Yksityiskohtainen view of ABB Type CLE Current Transformer nameplate

Kuva 2.4: An extreme close-up of the ABB Type CLE Current Transformer's nameplate. This view allows for clear reading of critical data such as "TYPE CLE", "CURRENT TX.", "S# 7524A63G05", "RATIO 6000:5 AMPS", "60 HZ", "NSV 0.6 KV", "BIL 10 KV", and "ANSI ACC. CL. METERING 0.3 B0.1 THRU B1.8". It also indicates "Made in U.S.A." and the manufacturer "ABB Power T&D Company Inc."

3. Turvallisuustiedot

VAROITUS: Sähköiskun vaara. Asennuksen ja huollon saa suorittaa vain pätevä henkilöstö.

  • Always de-energize the primary circuit before installing or servicing the current transformer.
  • Never open the secondary circuit of an energized current transformer. This can lead to dangerously high voltages and potential injury or equipment damage.
  • Varmista, että kaikki liitännät ovat tukevat ja asianmukaisesti eristettyjä.
  • Verify the correct polarity before connecting the CT to metering or protection devices.
  • Käytä asianmukaisia ​​henkilönsuojaimia (PPE) työskennellessäsi sähköjärjestelmien kanssa.

4. Asennus ja asennus

Installation of the ABB Type CLE Current Transformer requires adherence to local electrical codes and safety standards. It is recommended that a certified electrician or qualified technician perform the installation.

  1. Virran katkaiseminen piirissä: Ensure the primary circuit where the CT will be installed is completely de-energized and locked out according to safety protocols.
  2. Asennus: Securely mount the CT using appropriate hardware. The CT is designed to encircle the primary conductor.
  3. Primary Conductor: Pass the primary conductor through the center opening of the current transformer.
  4. Secondary Connections: Connect the secondary terminals (X1 and X2) to the metering or protection device. Observe correct polarity as indicated on the nameplate (H1-H2 for primary, X1-X2 for secondary). X1 typically corresponds to H1, and X2 to H2.
  5. Maadoitus: Ensure the secondary circuit of the CT is properly grounded at one point, typically at the X2 terminal, to prevent high voltage-kertymä.
  6. Tarkista yhteydet: Double-check all wiring for correctness and tightness.
  7. Re-energize: Once installation is complete and verified, the primary circuit can be safely re-energized.

5. Käyttöohjeet

The ABB Type CLE Current Transformer operates passively by inducing a proportional current in its secondary winding based on the primary current flowing through its core. Once installed, it requires no active user intervention for its primary function.

  • Valvonta: The output of the CT (typically 5 Amps at rated primary current) is fed into a connected meter, relay, or other monitoring device. Refer to the instruction manual of the connected device for its operation.
  • Load (Burden): Ensure the connected load (burden) on the secondary circuit does not exceed the CT's rated burden (e.g., B0.1 through B1.8 as indicated on the nameplate). Exceeding the burden can lead to inaccurate readings and potential damage.
  • Vastakkaisuus: Correct polarity is crucial for accurate directional measurements and proper operation of protective relays.

6. Huolto

The ABB Type CLE Current Transformer is designed for long-term, reliable operation with minimal maintenance. However, periodic inspections are recommended to ensure optimal performance and safety.

  • Silmämääräinen tarkastus: Periodically inspect the CT for any signs of physical damage, discoloration, or loose connections.
  • Puhdistus: If necessary, gently clean the exterior of the CT with a dry, lint-free cloth. Do not use abrasive cleaners or solvents. Ensure the power is off before cleaning.
  • Terminaalin tarkistus: Verify that all secondary terminal connections remain tight and free from corrosion. This should only be done with the primary circuit de-energized and the secondary circuit shorted or connected to a safe load.
  • Ympäristöolosuhteet: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent premature degradation.

7. Vianmääritys

Most issues related to current transformers stem from improper installation or external circuit problems. Always prioritize safety when troubleshooting.

OngelmaMahdollinen syyRatkaisu
No output from CT / Incorrect readings
  • Open secondary circuit
  • Incorrect wiring/polarity
  • Primary circuit de-energized
  • Faulty connected meter/device
  • CT burden exceeded
  • De-energize primary circuit. Check secondary connections for continuity and ensure they are properly terminated.
  • Verify wiring against schematic and nameplate.
  • Confirm primary circuit is energized and current is flowing.
  • Test connected device independently.
  • Reduce secondary load or replace CT with appropriate burden rating.
Overheating of CT
  • Overcurrent in primary circuit
  • Excessive secondary burden
  • Short circuit in secondary winding
  • Check primary circuit load.
  • Reduce secondary load.
  • De-energize primary circuit. Inspect secondary wiring for shorts.

If troubleshooting steps do not resolve the issue, contact ABB technical support or a qualified service professional.

8. Tekniset tiedot

The following specifications apply to the ABB Type CLE Current Transformer, Model 7524A63G05:

  • Mallinumero: 7524A63G05
  • Merkki: ABB (Asea Brown Boveri / ABB Power T&D Company Inc.)
  • Tyyppi: CLE Current Transformer
  • Current Ratio: 6000:5 Amps
  • Taajuus: 60 Hz
  • Nominal System Voitage (NSV): 0.6 kV
  • Basic Impulse Level (BIL): 10 kV
  • ANSI Accuracy Class: Metering 0.3 B0.1 THRU B1.8
  • Ulkomitat: Noin 30.5 cm x 33 cm x 7.6 cm
  • Inside Dimensions (Window): Noin 20.3 cm x 20.3 cm x 7.6 cm
  • Valmistajan osanumero: 236P750H07
  • UPC: 782451081325

9. Takuu ja tuki

For information regarding warranty coverage, technical support, or service for your ABB Type CLE Current Transformer, Model 7524A63G05, please contact ABB directly through their official website or customer service channels. Ensure you have your model number and any purchase details available when contacting support.

You can visit the official ABB weblisätietoa sivustolta: www.abb.com

Aiheeseen liittyvät asiakirjat - 7524A63G05

Preview MPF P Metering Panel Installation Instructions | ABB
Comprehensive installation guide for the ABB MPF P Metering Panel (2CGD001135S1000), covering safety, mounting, earthing, and circuit diagrams. Includes wire color references.
Preview ABB Virta ja JännitetagMittamuuntajat: Asennus-, käyttö- ja huolto-opas
Comprehensive guide from ABB detailing the installation, technical specifications, safety instructions, and maintenance procedures for Current and Voltage (potential) Instrument Transformers. It covers indoor and outdoor applications.
Preview ABB RET650 -muuntajan suojarele - Tuoteopas
Tutustu ABB:n RET650-releeseen, monipuoliseen muuntajan suojareleeseen, joka tarjoaa edistykselliset erotus-, impedanssi-, virta- ja jännitesuojaukset.tagja taajuussuoja sähköjärjestelmille. Tässä tuoteoppaassa on yksityiskohtaiset tiedot sen ominaisuuksista, sovelluksista ja teknisistä tiedoista luotettavaa sähköasema-automaatiota varten.
Preview ABB FH200A System pro M compact -vikavirtasuojakytkimen asennus ja tekniset tiedot
Kattava opas ABB:n FH200A System pro M -vikavirtasuojakytkimestä, joka kattaa tekniset tiedot, asennusohjeet, sähköliitännät ja turvallisuusohjeet.
Preview ABB DSH201R RCBO: Tekniset tiedot ja tiedot
Kattava tekninen datalehti ABB:n DSH201R-vikavirtasuojakytkimelle, jossa on ylivirtasuoja (RCBO). Tiedot sisältävät 4.5 kA:n katkaisukyvyn, AC-tyypin, 30 mA:n herkkyyden, C-laukaisukäyrän ja nimellisvirtavaihtoehdot 6–40 A. Ominaisuudet, sovellushyödyt, yksityiskohtaiset sähköiset ja mekaaniset tiedot, suorituskykytiedot eri olosuhteissa, mitat ja kytkentäkaaviot.
Preview ABB Ability™ Condition Monitoring for Electrical Systems – CMES User Management Quick Guide
A quick guide for managing users and credentials for the ABB Ability™ Condition Monitoring for electrical systems (CMES) solution, including creating new users, changing passwords, and network connectivity.