wattia 0063010

Watts 009M2 Alennetun paineen vyöhykkeen takaisinvirtauksenestolaite (malli 0063010) Käyttöohje

For Models: 009M2, 009M2-QT

1. Johdanto

This manual provides detailed instructions for the installation, operation, and maintenance of the Watts 009M2 Reduced Pressure Zone (RPZ) Backflow Preventer. This device is designed to protect potable water supplies from contamination due to backpressure or backsiphonage from non-potable sources. It is crucial to read and understand all instructions before installation and use to ensure proper function and safety.

The Watts 009M2 RPZ assembly features a compact, modular design for easy maintenance, with a single access cover for in-line repairs. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

2. Tärkeitä turvallisuustietoja

3. Tuote ohiview ja komponentit

The Watts 009M2 Reduced Pressure Zone Backflow Preventer is constructed with a durable bronze body and features NPT end connections. Key components include:

Watts 009M2 Reduced Pressure Zone Backflow Preventer
Figure 1: Watts 009M2 Reduced Pressure Zone Backflow Preventer. This image shows the bronze body, quarter-turn shutoff valves with green handles, and multiple test cocks on top.

4. Asennus ja asennus

  1. Asennusta edeltävä tarkistus:
    • Verify that the product model (009M2) and size (2 inch) match your requirements.
    • Tarkasta yksikkö mahdollisten kuljetusvaurioiden varalta.
    • Ensure all necessary tools and materials for installation are available.
  2. Sivuston valmistelu:
    • Choose an installation location that allows for easy access for testing and maintenance.
    • Ensure adequate drainage for the relief valve discharge.
    • The device should be installed horizontally, with the relief valve pointing downwards.
  3. Putkiliitos:
    • Flush the upstream piping thoroughly to remove any debris before connecting the backflow preventer.
    • Connect the inlet and outlet piping to the NPT connections on the device. Use appropriate thread sealant.
    • Avoid overtightening connections to prevent damage to the bronze body.
    • Ensure the flow arrow on the device body matches the direction of water flow.
  4. Relief Valve Drain:
    • Connect a drain line to the relief valve outlet. The drain line must be adequately sized and sloped to allow for free discharge and prevent backpressure on the relief valve.
    • Ensure the drain line terminates in an air gap, preventing any possibility of cross-connection.
  5. Asennuksen jälkeinen tarkistus:
    • Slowly open the upstream shutoff valve, then the downstream shutoff valve, to gradually fill the system and prevent water hammer.
    • Tarkasta kaikki liitännät vuotojen varalta.
    • Perform initial testing by a certified backflow prevention tester to ensure proper operation and compliance with local codes.

5. Käyttöohjeet

The Watts 009M2 is designed for continuous pressure operation. Normal operation involves the device being fully open, allowing water to flow through the system while providing backflow protection.

6. Huolto

Regular maintenance is critical for the reliable performance of your backflow preventer. The modular design and single access cover simplify servicing.

7. Vianmääritys

OngelmaMahdollinen syyRatkaisu
Water discharge from relief valve (continuous)
  • Fouled first check valve
  • Damaged relief valve seat or disc
  • Excessive backpressure
  • Clean or repair first check valve.
  • Inspect and replace relief valve components.
  • Identify and correct source of backpressure.
Ei veden virtausta tai virtaus on heikentynyt
  • Shutoff valves closed
  • Debris obstructing flow
  • Fouled check valves
  • Varmista, että sulkuventtiilit ovat täysin auki.
  • Isolate and inspect for debris.
  • Clean or repair check valves.
Vuodot liitoksista
  • Improperly sealed threads
  • Vaurioituneet tiivisteet
  • Re-apply thread sealant and tighten connections.
  • Inspect and replace gaskets.

For issues not listed or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Watts technical support.

8. Tekniset tiedot

Mallinumero0063010 (009M2)
Backflow Preventer TypeAlennettu painevyöhykekokoonpano
Rungon materiaaliPronssi
Tulo-/lähtöliitännän koko2 Inches (50 MM)
Inlet/Outlet Connection TypeFemale Threaded NPT
Suurin työpaine175 PSI (12.10 baaria)
Maksimilämpötila180 °F (82 °C)
Alin lämpötila33 °F (0.5 °C)
SuojaustyyppiBackpressure and Backsiphonage
Tuotteen mitat (P x L x K)22 x 10 x 8 tuumaa
Tuotteen paino27 puntaa
Lead Free StatusNO (For non-potable use only)

9. Takuu ja tuki

Specific warranty information for Watts products is typically provided with the product packaging or available on the official Watts websivusto. Katso näistä resursseista ajankohtaisimmat takuuehdot.

For technical support, replacement parts, or further assistance, please contact Watts customer service or visit their official website. Ensure you have your product model number (0063010) and serial number (if applicable) ready when contacting support.

Wattsin virallinen Websivusto: www.watts.com

Aiheeseen liittyvät asiakirjat - 0063010

Preview Wattsin LF909-sarjan alennetun paineen vyöhykekokoonpanon tekniset tiedot
Kattavat tekniset tiedot Watts LF909 -sarjan alennetun paineen vyöhykekokoonpanolle (21⁄2" - 10"). Yksityiskohtaiset tiedot tämän lyijyttömän takaisinvirtauksen estolaitteen ominaisuuksista, toiminnasta, materiaaleista, mitoista ja kapasiteetista, jossa on integroitu tulva-anturi.
Preview Watts-sarjat 009, LF009, LFU009, SS009, U009: Asennus-, huolto- ja korjausopas
Tämä kattava Wattsin käyttöohje tarjoaa olennaisia ​​ohjeita 009-, LF009-, LFU009-, SS009- ja U009-sarjan alennetun paineen vyöhykekokoonpanojen asennukseen, huoltoon ja korjaukseen. Se kuvaa yksityiskohtaisesti näiden kriittisten takaisinvirtauksen estolaitteiden turvallisuusvaroitukset, asennusmenettelyt, tarkastukset, huollot, vianmäärityksen ja takuutiedot.
Preview Watts Series 909, LF909, 909RPDA Reduced Pressure Zone Assemblies Installation, Maintenance, and Repair Manual
Comprehensive guide for the installation, maintenance, and repair of Watts Series 909, LF909, and 909RPDA Reduced Pressure Zone Assemblies, including safety warnings, installation guidelines, testing procedures, servicing instructions, troubleshooting, and warranty information.
Preview Watts-sarjan LF909 alennetun paineen vyöhykekokoonpanot - Tekniset tiedot
Watts-sarjan LF909 alennetun paineen vyöhykekokoonpanojen yksityiskohtaiset tekniset tiedot, mukaan lukien ominaisuudet, toiminta, mitat, painot ja kapasiteetti. Suunniteltu juomaveden ristiinkytkentään.
Preview Watts-sarjan 009, LF009, LFU009, SS009, U009 alennetun paineen vyöhykekokoonpanojen asennus-, huolto- ja korjausopas
Comprehensive guide for the installation, maintenance, and repair of Watts Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies, covering safety, installation procedures, annual inspection, troubleshooting, and service. Includes details on flood sensor activation and connection kits.
Preview Watts Series LF009 Reduced Pressure Zone Assembly - Technical Specifications
Detailed engineering specifications for the Watts Series LF009 Reduced Pressure Zone Assembly, including features, materials, dimensions, pressure ratings, and performance data for sizes 1/4" to 3".