1. Johdanto
The MCR SINOTIMER SVP-915A is an advanced adjustable voltage protector designed to safeguard electrical appliances and systems from voltage fluctuations and overcurrent conditions. It features an LCD display for real-time monitoring of voltage, current, and power consumption (KWH). This device integrates over-voltage, altage, and overload protection functions, automatically disconnecting the power supply when abnormal conditions are detected and reconnecting when safe levels are restored. It is suitable for DIN rail mounting in various electrical distribution systems.
2. Turvallisuustiedot
Please read this manual carefully before installation and operation. Failure to follow these instructions may result in electric shock, fire, or damage to the device and connected equipment.
- Ammattimainen asennussuositus: Asennuksen saa suorittaa vain pätevä sähköasentaja tai muu vastaava henkilö.
- Virran katkaisu: Always ensure the main power supply is disconnected before installing, wiring, or performing any maintenance on the device.
- Oikea johdotus: Follow the wiring diagram precisely. Incorrect wiring can cause damage or malfunction.
- Toimintaympäristö: Do not install the device in environments with excessive moisture, dust, corrosive gases, or high temperatures.
- Kantavuus: Do not exceed the maximum rated current and voltage laitteesta.
- Maadoitus: Varmista sähköjärjestelmän asianmukainen maadoitus.
3. Tuote ohiview
The SINOTIMER SVP-915A is a compact and versatile protection device. Its main components and features include:
- LCD-näyttö: Näyttää reaaliaikaisen äänenvoimakkuudentage (U), current (A), and accumulated power consumption (KWH).
- Ohjauspainikkeet: "SET" button for entering settings mode, and "Up" / "Down" arrow buttons for adjusting parameters.
- Tulo/lähtöliittimet: Clearly marked 'IN' (Input) and 'OUT' (Output) terminals for Live (L) and Neutral (N) connections.
- Asennus DIN-kiskoon: Suunniteltu helppoon asennukseen vakiomallisiin 35 mm:n DIN-kiskoihin.
- Suojaustoiminnot:
- Yli-voltage -suoja (OVP)
- Alivtage-suoja (UVP)
- Ylivirtasuoja (OCP)
- Automatic re-connection after fault clearance

Kuva 3.1: Etuosa view of the SINOTIMER SVP-915A, showing the LCD screen and control buttons.

Kuva 3.2: Kulmassa view of the device, showing the 'IN' and 'OUT' terminals.
4. Asennus ja asennus
Before proceeding with installation, ensure all safety precautions are observed, especially disconnecting the main power supply.
4.1. Asennus DIN-kiskoon
- Locate an appropriate 35mm DIN rail within your electrical panel.
- Align the device's mounting clip with the DIN rail.
- Press the device firmly onto the rail until it clicks into place. Ensure it is securely fastened.

Kuva 4.1: Pohja view havainnollistaa DIN-kiskon kiinnitysmekanismia.
4.2. Johdotusliitännät
Refer to the wiring diagram below for correct connection. The device is designed for single-phase systems.

Figure 4.2: Wiring Diagram for SINOTIMER SVP-915A.
- Tulo (IN): Connect the incoming Live (L) and Neutral (N) wires from your power source (e.g., main breaker or power switch) to the 'IN' terminals of the SVP-915A.
- Lähtö (OUT): Connect the outgoing Live (L) and Neutral (N) wires to your load (e.g., distribution panel or appliances) from the 'OUT' terminals of the SVP-915A.
- Varmista, että kaikki liitännät ovat tiukat ja turvalliset, jotta vältetään löysiä kontakteja ja ylikuumenemista.
4.3. Ensimmäinen käynnistys
After verifying all connections, restore power to the circuit. The device's LCD display should illuminate, showing the current voltage. The device will perform a self-test and then enter normal operating mode.
5. Käyttöohjeet
5.1. Näyttötilat
The LCD continuously displays the current voltage (U). Pressing the "Up" or "Down" buttons briefly will cycle through other display parameters:
- Voitage (U): Current line voltage voltteina (V).
- Nykyinen (A): Current load in Amperes (A).
- Teho (W): Real-time power consumption in Watts (W).
- Energy (KWH): Accumulated power consumption in Kilowatt-hours (KWH).
5.2. Suojausparametrien säätäminen
To enter the settings mode and adjust protection thresholds:
- Press and hold the "SET" button for approximately 3-5 seconds until the display starts flashing, indicating entry into settings mode.
- Use the "SET" button to cycle through the adjustable parameters:
- Yli-voltage protection threshold (UVP): Aseta suurin sallittu tilavuustage.
- Alivtage protection threshold (OVP): Aseta sallittu vähimmäistilavuustage.
- Over-current protection threshold (OCP): Set the maximum allowable current.
- Reconnection delay time: Time before the device reconnects after a fault.
- While a parameter is flashing, use the "Up" and "Down" arrow buttons to adjust its value.
- After setting all desired parameters, press and hold the "SET" button again for 3-5 seconds, or wait for 10 seconds without any button press, to save the settings and exit the settings mode.
5.3. Resetting KWH
To reset the accumulated KWH reading, enter the settings mode, navigate to the KWH display, and then press and hold both "Up" and "Down" buttons simultaneously until the KWH value resets to zero.
6. Huolto
The SINOTIMER SVP-915A is designed for minimal maintenance. However, periodic checks can ensure optimal performance and longevity.
- Puhdistus: Gently wipe the device with a dry, soft cloth to remove dust. Do not use liquid cleaners or abrasive materials.
- Yhteyden tarkistus: Periodically inspect wiring connections to ensure they remain tight and free from corrosion. (Ensure power is disconnected before inspection).
- Ympäristöolosuhteet: Ensure the operating environment remains within specified limits (temperature, humidity).
7. Vianmääritys
If you encounter issues with your SVP-915A, refer to the following common problems and solutions:
| Ongelma | Mahdollinen syy | Ratkaisu |
|---|---|---|
| Ei näyttöä / Laite ei käynnisty | No input power; Incorrect wiring; Device fault. | Check main power supply. Verify input wiring (L and N). If power is present and wiring is correct, the device may be faulty. |
| Device trips frequently | Yli-voltage, altage, or over-current condition; Protection thresholds set too low/high. | Tarkista todellinen linjan tilavuustage and load current. Adjust protection thresholds if necessary (refer to Section 5.2). Reduce load if over-current is detected. |
| Näytöllä näkyvät virheelliset lukemat | Wiring error; Device calibration issue. | Verify wiring connections. If readings are consistently inaccurate, the device may require service. |
| Device does not reconnect after fault | Fault condition still present; Reconnection delay too long; Device fault. | Ensure the fault condition (over/under voltage, over current) has cleared. Check reconnection delay setting. If the fault has cleared and delay passed, device may be faulty. |
Jos ongelma jatkuu näiden ratkaisujen kokeilemisen jälkeen, ota yhteyttä asiakastukeen.
8. Tekniset tiedot
Key technical specifications for the MCR SINOTIMER SVP-915A:
- Malli: SVP-915A
- Merkki: MCR (Manufacturer: SINOTIMER)
- Rated Voltage: 110V / 120V AC
- Arvioitu nykyinen: 63A (säädettävä)
- Yli-voltage Protection Range: Säädettävä
- Alivtage Protection Range: Säädettävä
- Over-current Protection Range: Säädettävä
- Näyttö: LCD (äänenvoimakkuustage, Current, KWH)
- Asennus: 35 mm DIN-kisko
- ASIN: B08C7NL296
- Osanumero: SVP915A-1
8.1. Mitat

Kuva 8.1: Laitteen mitat.
- Korkeus: Noin 85 mm
- Leveys: Noin 36 mm
- Syvyys: Approximately 65mm (including DIN rail clip)
9. Takuu ja tuki
For warranty information and technical support, please refer to the purchase documentation or contact your retailer. Keep your purchase receipt as proof of purchase.
For further assistance, you may also contact the manufacturer, SINOTIMER, through their official channels.