UEi Test Instruments IRT803
UEi IRT803 -eristysresistanssimittarin käyttöohje
Model: IRT803 | Brand: UEi Test Instruments
1. Johdanto
This manual provides essential information for the safe and effective operation of the UEi IRT803 Digital Insulation Resistance Tester. The IRT803 is a versatile instrument designed for measuring insulation resistance, AC/DC voltage, and continuity. It features a 1000V AC/DC measurement capability, auto-ranging, a backlit display, and a DMM rotary style selector. Key functions include Lock, Compare, and Polarization Index (PI)/Dielectric Absorption Ratio (DAR) tests. Please read this manual thoroughly before use to ensure proper handling and to maximize the instrument's performance.
2. Turvallisuustiedot
Always adhere to safety precautions when using electrical testing equipment. The IRT803 is designed with safety in mind, featuring a CATIV rating up to 600V and CATII up to 1000V, ensuring protection in various jobsite environments. Failure to follow safety instructions can result in electric shock, fire, or damage to the instrument.
- Älä käytä testeriä, jos se näyttää vaurioituneelta tai jos mittausjohdot ovat vaurioituneet.
- Varmista, että oikea toiminto ja mittausalue on valittu ennen mittausten tekemistä.
- Always disconnect power to the circuit under test before connecting or disconnecting test leads for resistance measurements.
- Käytä asianmukaisia henkilönsuojaimia, kuten eristettyjä käsineitä ja suojalaseja.
- Do not operate the tester in wet conditions or in the presence of explosive gases or dust.
- Vaihda paristot viipymättä, kun heikon pariston varoitusvalo tulee näkyviin, jotta mittaustulokset ovat tarkkoja.
3. Mitä laatikossa on
Pura pakkausta pakkauksesta ja varmista, että kaikki alla luetellut osat ovat mukana ja vahingoittumattomia:
- UEi IRT803 Insulation Resistance Tester
- Silicone test leads with alligator clips (red and black) (ATL57)
- Insulation test probe with alligator clips (red & black)
- 4 AA-paristoa
- Käyttöopas
- Pehmeä kantolaukku

Image 3.1: All components included with the UEi IRT803 Insulation Resistance Tester, including the meter, test leads, probes, batteries, manual, and soft carrying case.
4. Tuote ohiview
The IRT803 is designed for ease of use and durability. It features an easy-to-read LCD display with a backlight for visibility in various lighting conditions, and a work light to illuminate dark environments. The unit is protected by a rugged rubber boot, which also includes convenient test lead holders for compact storage. An auto power-off function helps conserve battery life.
4.1. Tärkeimmät ominaisuudet ja toiminnot
- 600V AC/DC Measurement: Pystyy mittaamaan sekä vaihto- että tasavirtaatag600V asti.
- Eristysvastus: Measures resistance from 0.01MΩ up to 2GΩ with test voltages of 50V, 100V, 250V, 500V, and 1000V.
- Jatkuvuus: Virtapiirin jatkuvuuden tarkistamiseen.
- Compare Reading Function: Allows for comparison against a set reference value.
- PI/DAR-testi: Automatic calculation of Polarization Index and Dielectric Absorption Ratio for advanced insulation diagnostics.
- A-Hold/Hold: Jäädyttää näytetyn lukeman kätevää tallennusta varten.
- Lock Reading: Locks the test voltage for continuous insulation testing.
- Rotary Dial Selector: Intuitive selection of measurement functions and test voltages.
- Suojaava kumisaapas: Enhances durability and provides lead storage.

Kuva 4.1: Edessä view of the IRT803 showing the LCD display, rotary selector, and function buttons.

Image 4.2: Visual representation highlighting the main functions and features of the IRT803.
5. Asennus
5.1. Akun asennus
The IRT803 requires four (4) AA batteries for operation. To install or replace batteries:
- Varmista, että testeri on sammutettu.
- Paikanna paristolokero laitteen takaosasta.
- Avaa paristolokeron kansi ruuvimeisselillä.
- Aseta neljä AA-paristoa paikoilleen ja huomioi oikea napaisuus (+/-) lokeron sisällä olevien merkkien mukaisesti.
- Sulje paristolokeron kansi kunnolla.
5.2. Testijohtojen liittäminen
Connect the test leads to the appropriate input jacks on the tester. For most measurements, the red lead connects to the 'V Ω INSULATION' jack and the black lead connects to the 'COM' (common) jack. Ensure connections are firm and secure.

Image 5.1: The IRT803 with test leads properly connected to the input jacks.
6. Käyttöohjeet
6.1. Powering On/Off and Display Backlight
- To power on the unit, rotate the selector dial from 'OFF' to any desired measurement function.
- To power off, rotate the selector dial back to 'OFF'. The unit also features auto power-off to save battery life after a period of inactivity.
- Paina VALITSE button (often indicated by a light bulb icon) to toggle the display backlight on or off.
6.2. Eristyskestävyystestaus
The IRT803 can perform insulation resistance tests at various voltages.
- Valitse testimäärätage: Rotate the selector dial to the desired insulation test voltage (50V, 100V, 250V, 500V tai 1000V).
- Kytke mittausjohdot: Connect the red test lead to the circuit under test and the black test lead to the ground or common point. Ensure the circuit is de-energized.
- Aloita testi: Press and hold the large red TESTATA button to begin the insulation test. The test voltage will be applied, and the resistance reading will be displayed.
- Lukitustoiminto: For continuous testing, press the LUKKO button after initiating the test. This will maintain the test voltage without needing to hold the TESTATA -painiketta. Lehdistö TESTATA uudelleen lukituksen avaamiseksi.
- Compare Function: Käytä VERRATA button to set a reference value and compare subsequent readings against it.
- PI/DAR-testi: Select the PI/DAR function on the dial. The meter will automatically perform the Polarization Index and Dielectric Absorption Ratio tests, displaying the calculated values.
- Read and Record: Observe the reading on the LCD. Use the PIDÄ button to freeze the display for easier recording.
- Purkaus: After completing an insulation test, the circuit under test should be discharged. The IRT803 typically handles this automatically, but always exercise caution.

Image 6.1: The IRT803 being used to measure insulation resistance on electrical wiring.

Kuva 6.2: Lähikuva view of the test leads securely connected to the IRT803's input terminals.
6.3. Voitage Testing (AC/DC)
AC tai DC voltage up to 600V:
- Rotate the selector dial to the 'V' position.
- Connect the red test lead to the positive or live point and the black test lead to the negative or neutral/ground point of the circuit.
- Näytössä näkyy mitattu tilavuustage. Mittari havaitsee automaattisesti vaihto- tai tasavirrantage.
6.4. Jatkuvuuden testaus
To check for continuity in a circuit:
- Rotate the selector dial to the 'Ω' (Ohms) position, which typically includes continuity.
- Connect the test leads across the component or circuit path you wish to test.
- If there is continuity (low resistance), the meter will typically emit an audible beep and display a low resistance value.
7. Huolto
7.1. Puhdistus
To maintain the accuracy and longevity of your IRT803:
- Pyyhi casing mainoksellaamp liinalla ja miedolla pesuaineella. Älä käytä hankaavia aineita tai liuottimia.
- Ensure the unit is completely dry before storage or next use.
7.2. Pariston vaihto
Replace batteries as described in Section 5.1 when the low battery indicator appears on the display. Always use fresh AA alkaline batteries.
7.3. Varastointi
When not in use, store the IRT803 in its soft carrying case in a cool, dry environment, away from direct sunlight and extreme temperatures. If storing for extended periods, remove the batteries to prevent leakage.
8. Vianmääritys
If you encounter issues with your IRT803, refer to the following common problems and solutions:
| Ongelma | Mahdollinen syy | Ratkaisu |
|---|---|---|
| Testeri ei käynnisty | Tyhjät tai väärin asennetut paristot | Tarkista paristojen napaisuus; vaihda tilalle uudet AA-paristot. |
| No reading on display | Incorrect function selected; open circuit; poor test lead connection | Verify selector dial position; ensure test leads are firmly connected to the circuit and the meter; check for breaks in the circuit. |
| Epätarkkoja lukemia | Low battery; environmental interference; incorrect range/function | Replace batteries; move away from strong electromagnetic fields; ensure correct function and test voltage are selected. |
| Test leads not working | Damaged leads; poor connection | Inspect leads for damage; ensure they are fully inserted into the jacks. Replace if damaged. |
If the problem persists after attempting these solutions, please contact UEi Test Instruments customer support.
9. Tekniset tiedot
| Parametri | Arvo |
|---|---|
| Mallinumero | IRT803 |
| Merkki | UEi-testauslaitteet |
| Eristystesti Voitages | 50V, 100V, 250V, 500V, 1000V |
| Eristysvastusalue | 0.01MΩ to 2GΩ |
| Insulation Resistance Accuracy | ±1.5-3% + 5 digits (0.01MΩ-500MΩ) |
| Voitage Mittaus | Jopa 600 V AC/DC |
| Jatkuvuusalue | 20.00 Ω to 20.0 kΩ (as per product description) |
| Turvallisuusluokitus | CATIV 600V, CATII 1000V |
| Virtalähde | 4 x AA-paristot |
| Näyttö | LCD-näyttö taustavalolla |
| Tuotteen mitat | 2.7 x 3.52 x 8.27 tuumaa |
| Tuotteen paino | 1.8 puntaa |
| Väri | Keltainen |
10. Takuutiedot
The UEi IRT803 Insulation Resistance Tester is backed by a 1 vuoden rajoitettu takuu from the date of purchase. This warranty covers defects in materials and workmanship under normal use. It does not cover damage resulting from misuse, unauthorized modification, accident, or neglect. For specific terms and conditions, please refer to the warranty card included with your product or contact UEi Test Instruments customer support.

Kuva 10.1: Esim.ample of a Certificate of Conformity, indicating adherence to quality standards.
11. Tukea
For technical assistance, troubleshooting beyond this manual, or warranty claims, please contact UEi Test Instruments customer support. You can find more information and contact details by visiting the official UEi Test Instruments websivustolla tai heidän Amazon-kauppasivullaan.
UEi Test Instruments Store: Käy myymälässä
Ask a question about this manual
Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.